Number of clamps/phases

Hey,

I'm having 2 phases that i would like to monitor. So i bought 2 clamps of 50. However I couldn't find any documentation how the settings should be for the sensor (Current clamp ports & Number of phases).

For the moment, i've got 'clamp ports: 3' en 'phases: 1'.
When i put someting else, i don't have any output of the sensors?
So i think that these settings are correct?

But i've got some doubts of the values that i see. :$
Is there any information who these settings should be?

gebhardm's picture

Current clamp ports 3; number of phases 1 - this means that per clamp port one phase is measured and clamp ports 1 to 3 are not summed up; if you have just two phases, leave clamp port 3 disabled...

gebhardm's picture

Why do you doubt your readings? looks ok - the atelier consumes some power while in the house just a fridge seems to be running...

OnIrIa's picture

Ahh, make sense now...
Thanks!

Yep, values look ok now. The house is almost in sleep mode now (like you said, just fridge & freezer). The atelier is having a server, switch... so this looks also normal.
I think i had a bad unit selection when i looked at it. :$

I think the biggest problem today is the way how to look at it.
I mean, it's a bit difficult to understand all options (like the units...). Maybe a good manual could be a big adventage for flukso. Today, it's a bit hard to find all this kind of information... :$